Sign In | Join Free | My qualitytoyschina.com
China Knkong Electric Co.,Ltd logo
Knkong Electric Co.,Ltd
Knkong Electric Co.,Ltd
Active Member

5 Years

Home > VCB Circuit Breaker >

Environmental Protection Vacuum Circuit Breaker 24KV 630A

Knkong Electric Co.,Ltd
Contact Now

Environmental Protection Vacuum Circuit Breaker 24KV 630A

Brand Name : KNKONG

Model Number : VS1-12

Certification : CB,ISO,IEC

Place of Origin : China

MOQ : 1

Payment Terms : L/C, T/T, Western Union

Supply Ability : 1000 Unit per month

Delivery Time : 15 working days

Packaging Details : Standard export packaging

Voltage : 12KV-24KV

Current : 630A-2000A

Breaking current : 25KA

Type : Fixed type

Original : Zhengzhou, CHINA

Manufactory : KNKONG

Contact Now

Vacuum circuit breaker VS1-12 indoor use environmental protection type

Voltage: 12KV-24KV

Current: 630A-2000A

Breaking current: 20KA-25KA

Type: Fixed

Product overview

VS1-12 type vacuum circuit breaker is an indoor high-voltage switchgear, which is suitable for three-phase power system with rated voltage of 12kV and frequency of 50Hz. place.

Technical Parameters

No. Item Unit Parameter
1 Rated voltage KV 12
2 Rated frequency Hz 50/60
3

Rated insulation level

1min power frequency withstand voltage(r. m. s)

KV

42(phase-to-phase, phase-to-earth)

48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase, phase-to-earth)

85(across the isolating distance)

4

Rated current

A

630 630 1250 1600
1250 1250 1600 2000
2000 2500
2500 3150
4000
5 Rated short-circuit breaking current

KA

20 25 31.5 40
6 Rated short-time withstand current 20 25 31.5 40
7 Rated short-circuit marking current 50 63 80 100
8 Rated peak withstand current 50 63 80 100
9 Rated duration of short-circuit s 4
10 Rated operating sequence O-0.3s-O/C-180s-O/C
11 Breaking times of rated short-circuit current Times 30/20 times(40KA)
12 Mechanical endurance Ops 20000
13 Rated single capacitor bank breaking current

A

630
14 Rated back-to-back capacitor bank breaking current 400
15 Double-earth fault breaking current 27.4
16 Allowable maximum contact erosion

mm

3
17 Clearance between open contacts 10±1
18 Over stroke 3.5±0.5
19 Non-simultaneity of 3-phase opening and closing

ms

≤2
20 Bounce duration of contact closing ≤2
21 Average breaking speed (instant breaking 6mm)

m/s

1.1±0.2
22 Average making speed 0.8±0.2
23 Making time

ms

≤100
24 Breaking time ≤50

25

Resistance of each phase main circuit

μ Ω

630A ≤50
1250A ≤45
1600A~2000A ≤35
≥2500A ≤25
26 Contact breaking bounce amplitude mm ≤2

27

Rated operating voltage Rated operating voltage(V)AC/DC

V

24* 110 220
Scope of normal operation voltage Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
28 Rated voltage of energy storage motor V AC110/220,DC110/220
29 Energy storage time S ≤15

Environmental Protection Vacuum Circuit Breaker 24KV 630A


Product Tags:

IEC Environmental Protection VCB Circuit Breaker

      

Vacuum Circuit Breaker 24KV

      

Vacuum Circuit Breaker 630A

      
Quality Environmental Protection Vacuum Circuit Breaker 24KV 630A wholesale

Environmental Protection Vacuum Circuit Breaker 24KV 630A Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Knkong Electric Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)